Hayman Solar Farm — unit zero

QLD · System Strength · Q_2+1_R3_HAYMSF1
Most frequent constraint: Limit Hayman SF to100%,70%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Period, last 90 days (27 Aug 2026 to 24 Nov 2026, 2,160 hours).
Binding hours
139
% of period
6.4%
Network as built share
0.0%
Equipment outage share
0.0%
Single-plant limit share
100%
Units in constraints
1
MW in constraints
58
Curtailed while constrained
2.2 GWh
Value of that curtailment
$0.0m

Constraint-hours by cause, per month

Network as builtEquipment outageLimit on a single plant

Constraints that bound in the period

ConstraintHoursCauseLimit typeAEMO description
Q_2+1_R3_HAYMSF128Limit on a single plantSystem StrengthLimit Hayman SF to100%,70%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_A39B_HAYMSF127Limit on a single plantSystem StrengthLimit Hayman SF to 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+LCCP_HAYMSF126Limit on a single plantSystem StrengthLimit Hayman SF to 100%, 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+BSNE_HAYMSF121Limit on a single plantSystem StrengthLimit Hayman SF to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_A39_HAYMSF116Limit on a single plantSystem StrengthLimit Hayman SF to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+1_R4_HAYMSF112Limit on a single plantSystem StrengthLimit Hayman SF to100%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+1_R2_HAYMSF16Limit on a single plantSystem StrengthLimit Hayman SF to100%,80%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+3+VC_HAYMSF16Limit on a single plantSystem StrengthLimit Hayman SF to 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+RSVC_HAYMSF11Limit on a single plantSystem StrengthLimit Hayman SF to 100%, 80%, 60%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_A39C_HAYMSF10Limit on a single plantSystem StrengthLimit Hayman SF to 80%,70%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_STR_NIL_HAYMSF10Limit on a single plantSystem StrengthLimit Hayman SF to 100%, 70%, 60% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville/Clarke Creek Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_A19A_HAYMSF10Limit on a single plantSystem StrengthLimit Hayman SF to 80%, 40%, 0% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition

Units behind it

UnitFuelMWWeightDirection
Hayman Solar FarmSolar581.00discharge

Associated outages

SubstationEquipmentStartEndStatusReasonBinding hours (whole outage)
275KV_8859, H58_LARCLINE 275KV_885921 Sep 2026 07:002 Oct 2026 17:00COMPLETEHV equipt maintenance27
H29_STAN, H24_CALVCB CPLR_5052, LINE 275KV_855, CB 5012, CB FDR_855214 Sep 2026 08:301 Oct 2026 18:00COMPLETEHV equipt commissioning27
H20_BSND, H11_NEBOCB FDR_88462, CB CPLR_5062, LINE 275KV_8846, CB CPLR_50427 Sep 2026 07:0013 Sep 2026 11:30COMPLETEHV equipt commissioning26
H170_GLN, H20_BSNDCB CPLR_5042, LINE 275KV_8720, CB FDR_87192, CB FDR_8720213 Sep 2026 12:0020 Sep 2026 17:00COMPLETEHV equipt commissioning16
H170_GLN, H11_NEBOLINE 275KV_8846N, CB CPLR_5062, CB FDR_88462, CB CPLR_5022, CB FDR_87192, CB FDR_8720213 Sep 2026 12:0020 Sep 2026 17:00COMPLETEHV equipt commissioning16
H35_STHM, H11_NEBOCB FDR_8222, CB CPLR_5062, LINE 275KV_82212 Sep 2026 07:0012 Sep 2026 17:00COMPLETEHV equipt maintenance4
H35_STHMCB CPLR_5072, SVC 1_H35, CB SVC_581212 Sep 2026 07:0012 Sep 2026 17:00COMPLETEHV equipt commissioning4
H35_STHM, H11_NEBOLINE 275KV_822, CB FDR_8222, CB CPLR_506211 Sep 2026 07:0011 Sep 2026 17:00COMPLETEHV equipt maintenance3
H35_STHMCB CPLR_5072, CB SVC_5812, SVC 1_H3511 Sep 2026 07:0011 Sep 2026 17:00COMPLETEHV equipt commissioning3
H20_BSND, H11_NEBOCB CPLR_5062, CB FDR_88462, CB CPLR_5042, LINE 275KV_88469 Sep 2026 07:3013 Sep 2026 13:30COMPLETEHV equipt commissioning3
H20_BSNDCB FDR_89252, CB FDR_8562, CB CPLR_5042, CB FDR_88312, CB FDR_89342, BUS 1, CB FDR_82023 Oct 2026 09:306 Oct 2026 16:00COMPLETEHV equipt commissioning2
H13_ROSSCB CPLR_5022, CB SVC_5812, SVC 1_H1323 Sep 2026 13:3224 Sep 2026 17:00COMPLETEHV equipt maintenance1
H13_ROSSCB CPLR_5022, CB SVC_5812, SVC 1_H1323 Sep 2026 20:0024 Sep 2026 12:00COMPLETEHV equipt maintenance1
H6_GNGN, 275KV_814/2LINE 275KV_814/2, CB FDR_814226 Oct 2026 10:0030 Oct 2026 17:00COMPLETEHV equipt maintenance0
H20_BSNDCB FDR_8831226 Oct 2026 08:0026 Oct 2026 16:00COMPLETEHV equipt maintenance0
H58_LARC, 275KV_8859LINE 275KV_885926 Oct 2026 09:0030 Oct 2026 17:00COMPLETEHV equipt maintenance0
H29_STANCB 5022, CB FDR_8632, CB FDR_8642, CB FDR_8612, LINE 275KV_8982, CB FDR_8622, BUS 12, CB FDR_883128 Oct 2026 09:008 Oct 2026 16:00COMPLETEHV equipt maintenance0
H29_STANCB FDR_86428 Oct 2026 08:0010 Oct 2026 16:30COMPLETEHV equipt maintenance0
Source: AEMO. Summary built 25 Nov 2026 02:41; data through 25 Nov 2026 01:40 NEM time. “Intervals limited” measures exposure (a binding constraint that includes the unit), not lost output. “Curtailed while constrained” is the unit’s curtailment in intervals when such a constraint was binding, valued at the regional price with negative prices counted as zero. Constraint definitions arrive from AEMO about a month after the event, so recent constraints show “description pending”.