| Q_2+LCCP_KEP | 107 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to 100%, 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_2+BSNE_KEP | 90 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_2+1_R4_KEP | 54 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to100%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_A39B_KEP | 39 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_2+1_R3_KEP | 36 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to100%,70%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_2+3+VC_KEP | 16 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_A39_KEP | 15 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_2+1_R2_KEP | 8 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to100%,80%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_2+RSVC_KEP | 4 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to 100%, 80%, 60%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_KEP-HYB_50MW | 1 | Limit on a single plant | Discretionary | Kennedy Energy Park upper limit of 50MW |
| Q_STR_NIL_KEP | 0 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to 100%, 70%, 60% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville/Clarke Creek Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_A19A_KEP | 0 | Limit on a single plant | System Strength | Limit Kennedy Energy Park to 80%, 40%, 0% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |