NEM Dashboard

ITK
Period

Kennedy Energy Park — system strength

QLD · System Strength · Q_2+LCCP_KEP
Most frequent constraint: Limit Kennedy Energy Park to 100%, 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Period, last 90 days (27 Aug 2026 to 24 Nov 2026, 2,160 hours).
Binding hours
367
% of period
17%
Network as built share
0.0%
Equipment outage share
0.0%
Single-plant limit share
100%
Units in constraints
2
MW in constraints
58
Curtailed while constrained
4.1 GWh
Value of that curtailment
$0.3m

Constraint-hours by cause, per month

Network as builtEquipment outageLimit on a single plant

Constraints that bound in the period

ConstraintHoursCauseLimit typeAEMO description
Q_2+LCCP_KEP107Limit on a single plantSystem StrengthLimit Kennedy Energy Park to 100%, 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_2+BSNE_KEP90Limit on a single plantSystem StrengthLimit Kennedy Energy Park to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_2+1_R4_KEP54Limit on a single plantSystem StrengthLimit Kennedy Energy Park to100%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_A39B_KEP39Limit on a single plantSystem StrengthLimit Kennedy Energy Park to 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_2+1_R3_KEP36Limit on a single plantSystem StrengthLimit Kennedy Energy Park to100%,70%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_2+3+VC_KEP16Limit on a single plantSystem StrengthLimit Kennedy Energy Park to 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_A39_KEP15Limit on a single plantSystem StrengthLimit Kennedy Energy Park to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_2+1_R2_KEP8Limit on a single plantSystem StrengthLimit Kennedy Energy Park to100%,80%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_2+RSVC_KEP4Limit on a single plantSystem StrengthLimit Kennedy Energy Park to 100%, 80%, 60%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_KEP-HYB_50MW1Limit on a single plantDiscretionaryKennedy Energy Park upper limit of 50MW
Q_STR_NIL_KEP0Limit on a single plantSystem StrengthLimit Kennedy Energy Park to 100%, 70%, 60% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville/Clarke Creek Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_A19A_KEP0Limit on a single plantSystem StrengthLimit Kennedy Energy Park to 80%, 40%, 0% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition

Units behind it

UnitFuelMWWeightDirection
Kennedy Energy Park - Phase 1 - WindWind431.00discharge
Kennedy Energy Park - Phase 1 - SolarSolar151.00discharge

Associated outages

SubstationEquipmentStartEndStatusReasonBinding hours (whole outage)
275KV_8859, H58_LARCLINE 275KV_885921 Sep 2026 07:002 Oct 2026 17:00COMPLETEHV equipt maintenance107
H29_STAN, H24_CALVCB FDR_8552, CB CPLR_5052, LINE 275KV_855, CB 501214 Sep 2026 08:301 Oct 2026 18:00COMPLETEHV equipt commissioning102
H170_GLN, H20_BSNDCB CPLR_5042, CB FDR_87192, LINE 275KV_8720, CB FDR_8720213 Sep 2026 12:0020 Sep 2026 17:00COMPLETEHV equipt commissioning55
H170_GLN, H11_NEBOCB CPLR_5022, CB FDR_87192, LINE 275KV_8846N, CB CPLR_5062, CB FDR_88462, CB FDR_8720213 Sep 2026 12:0020 Sep 2026 17:00COMPLETEHV equipt commissioning53
H20_BSND, H11_NEBOCB FDR_88462, CB CPLR_5062, LINE 275KV_8846, CB CPLR_50427 Sep 2026 07:0013 Sep 2026 11:30COMPLETEHV equipt commissioning36
H13_ROSSCB SVC_5812, CB CPLR_5022, SVC 1_H1323 Sep 2026 13:3224 Sep 2026 17:00COMPLETEHV equipt maintenance6
H13_ROSSCB CPLR_5022, CB SVC_5812, SVC 1_H1323 Sep 2026 20:0024 Sep 2026 12:00COMPLETEHV equipt maintenance6
H11_NEBO, H35_STHMCB CPLR_5062, LINE 275KV_822, CB FDR_822211 Sep 2026 07:0011 Sep 2026 17:00COMPLETEHV equipt maintenance5
H11_NEBO, H20_BSNDCB CPLR_5042, CB CPLR_5062, LINE 275KV_8846, CB FDR_884629 Sep 2026 07:3013 Sep 2026 13:30COMPLETEHV equipt commissioning5
H35_STHM, H11_NEBOCB FDR_8222, CB CPLR_5062, LINE 275KV_82212 Sep 2026 07:0012 Sep 2026 17:00COMPLETEHV equipt maintenance5
H35_STHMSVC 1_H35, CB CPLR_5072, CB SVC_581211 Sep 2026 07:0011 Sep 2026 17:00COMPLETEHV equipt commissioning5
H35_STHMSVC 1_H35, CB SVC_5812, CB CPLR_507212 Sep 2026 07:0012 Sep 2026 17:00COMPLETEHV equipt commissioning3
H13_ROSSCB SVC_5812, CB CPLR_5022, SVC 1_H1321 Sep 2026 19:4222 Sep 2026 00:30COMPLETEHV equipt maintenance1
H20_BSNDCB CPLR_5042, CB FDR_8562, CB FDR_89342, CB FDR_89252, BUS 1, CB FDR_88312, CB FDR_82023 Oct 2026 09:306 Oct 2026 16:00COMPLETEHV equipt commissioning0
Source: AEMO. Summary built 25 Nov 2026 02:26; data through 25 Nov 2026 01:25 NEM time. “Intervals limited” measures exposure (a binding constraint that includes the unit), not lost output. “Curtailed while constrained” is the unit’s curtailment in intervals when such a constraint was binding, valued at the regional price with negative prices counted as zero. Constraint definitions arrive from AEMO about a month after the event, so recent constraints show “description pending”.