| Q_HAMISF1_ZERO | 33 | Limit on a single plant | Unit Zero | Hamilton solar farm upper limit of 0 MW |
| Q_2+LCCP_HAMISF1 | 26 | Limit on a single plant | System Strength | Limit Hamilton SF to 100%, 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition |
| Q_A39B_HAMISF1 | 25 | Limit on a single plant | System Strength | Limit Hamilton SF to 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition |
| Q_2+1_R3_HAMISF1 | 24 | Limit on a single plant | System Strength | Limit Hamilton SF to100%,70%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition |
| Q_2+BSNE_HAMISF1 | 6 | Limit on a single plant | System Strength | Limit Hamilton SF to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition |
| Q_2+1_R4_HAMISF1 | 6 | Limit on a single plant | System Strength | Limit Hamilton SF to100%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition |
| Q_2+3+VC_HAMISF1 | 5 | Limit on a single plant | System Strength | Limit Hamilton SF to 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition |
| Q_2+1_R2_HAMISF1 | 5 | Limit on a single plant | System Strength | Limit Hamilton SF to100%,80%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition |
| Q_A39_HAMISF1 | 3 | Limit on a single plant | System Strength | Limit Hamilton SF to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition |
| Q_2+RSVC_HAMISF1 | 1 | Limit on a single plant | System Strength | Limit Hamilton SF to 100%, 80%, 60%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition |
| Q_A39C_HAMISF1 | 1 | Limit on a single plant | System Strength | Limit Hamilton SF to 80%,70%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition |
| Q_STR_NIL_HAMISF1 | 0 | Limit on a single plant | System Strength | Limit Hamilton SF to 100%, 70%, 60% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville/Clarke Creek Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |
| Q_A19A_HAMISF1 | 0 | Limit on a single plant | System Strength | Limit Hamilton SF to 80%, 40%, 0% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition |