Kidston Solar Project Phase One 50MW — system strength

QLD · System Strength · Q_STR_A19B_KIDSF
Most frequent constraint: Limit 80% to Kidston Solar Farm if Stan>=2+Cal>=1+Cal+Glad>=2+ (Stan+Cal+Glad) >=7, Kar>=2,NQLD>350&370(AVG),Ross_FN>150&170(AVG),(Townsville GT>=1if kar<2),40% If NQLD>50&70(AVG), Zero otherwise.
Period, last 90 days (27 Aug 2026 to 24 Nov 2026, 2,160 hours).
Binding hours
163
% of period
7.6%
Network as built share
0.0%
Equipment outage share
0.0%
Single-plant limit share
100%
Units in constraints
1
MW in constraints
50
Curtailed while constrained
3.1 GWh
Value of that curtailment
$0.1m

Constraint-hours by cause, per month

Network as builtEquipment outageLimit on a single plant

Constraints that bound in the period

ConstraintHoursCauseLimit typeAEMO description
Q_2+1_R3_KSP134Limit on a single plantSystem StrengthLimit Kidston SF to100%,70%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+BSNE_KSP131Limit on a single plantSystem StrengthLimit Kidston SF to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+LCCP_KSP130Limit on a single plantSystem StrengthLimit Kidston SF to 100%, 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_A39B_KSP127Limit on a single plantSystem StrengthLimit Kidston SF to 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_A39_KSP117Limit on a single plantSystem StrengthLimit Kidston SF to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+1_R2_KSP111Limit on a single plantSystem StrengthLimit Kidston SF to100%,80%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+1_R4_KSP19Limit on a single plantSystem StrengthLimit Kidston SF to100%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+3+VC_KSP18Limit on a single plantSystem StrengthLimit Kidston SF to 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+RSVC_KSP11Limit on a single plantSystem StrengthLimit Kidston SF to 100%, 80%, 60%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_STR_NIL_KSP10Limit on a single plantSystem StrengthLimit Kidston SF to 100%, 70%, 60% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville/Clarke Creek Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_A19A_KSP10Limit on a single plantSystem StrengthLimit Kidston SF to 80%, 40%, 0% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition

Units behind it

UnitFuelMWWeightDirection
Kidston Solar Project Phase One 50MWSolar501.00discharge

Associated outages

SubstationEquipmentStartEndStatusReasonBinding hours (whole outage)
H11_NEBO, H20_BSNDLINE 275KV_8846, CB CPLR_5062, CB FDR_88462, CB CPLR_50427 Sep 2026 07:0013 Sep 2026 11:30COMPLETEHV equipt commissioning32
H58_LARC, 275KV_8859LINE 275KV_885921 Sep 2026 07:002 Oct 2026 17:00COMPLETEHV equipt maintenance30
H29_STAN, H24_CALVCB 5012, CB FDR_8552, LINE 275KV_855, CB CPLR_505214 Sep 2026 08:301 Oct 2026 18:00COMPLETEHV equipt commissioning30
H170_GLN, H20_BSNDCB CPLR_5042, CB FDR_87192, LINE 275KV_8720, CB FDR_8720213 Sep 2026 12:0020 Sep 2026 17:00COMPLETEHV equipt commissioning24
H170_GLN, H11_NEBOCB CPLR_5022, CB FDR_87192, CB FDR_88462, CB CPLR_5062, LINE 275KV_8846N, CB FDR_8720213 Sep 2026 12:0020 Sep 2026 17:00COMPLETEHV equipt commissioning23
H35_STHM, H11_NEBOCB FDR_8222, LINE 275KV_822, CB CPLR_506211 Sep 2026 07:0011 Sep 2026 17:00COMPLETEHV equipt maintenance5
H35_STHMCB SVC_5812, SVC 1_H35, CB CPLR_507211 Sep 2026 07:0011 Sep 2026 17:00COMPLETEHV equipt commissioning5
H20_BSND, H11_NEBOCB CPLR_5042, CB FDR_88462, CB CPLR_5062, LINE 275KV_88469 Sep 2026 07:3013 Sep 2026 13:30COMPLETEHV equipt commissioning5
H35_STHM, H11_NEBOCB FDR_8222, CB CPLR_5062, LINE 275KV_82212 Sep 2026 07:0012 Sep 2026 17:00COMPLETEHV equipt maintenance5
H35_STHMSVC 1_H35, CB CPLR_5072, CB SVC_581212 Sep 2026 07:0012 Sep 2026 17:00COMPLETEHV equipt commissioning5
H20_BSNDCB FDR_88312, CB FDR_8562, CB CPLR_5042, CB FDR_89342, CB FDR_89252, BUS 1, CB FDR_82023 Oct 2026 09:306 Oct 2026 16:00COMPLETEHV equipt commissioning2
H13_ROSSCB CPLR_5022, CB SVC_5812, SVC 1_H1323 Sep 2026 13:3224 Sep 2026 17:00COMPLETEHV equipt maintenance1
H13_ROSSCB SVC_5812, CB CPLR_5022, SVC 1_H1323 Sep 2026 20:0024 Sep 2026 12:00COMPLETEHV equipt maintenance1
Source: AEMO. Summary built 25 Nov 2026 02:41; data through 25 Nov 2026 01:40 NEM time. “Intervals limited” measures exposure (a binding constraint that includes the unit), not lost output. “Curtailed while constrained” is the unit’s curtailment in intervals when such a constraint was binding, valued at the regional price with negative prices counted as zero. Constraint definitions arrive from AEMO about a month after the event, so recent constraints show “description pending”.