Rugby Run Solar Farm — system strength

QLD · System Strength · Q_STR_A19B_RUGSF
Most frequent constraint: Limit 80% to Rugby Run Solar Farm if Stan>=2+Cal>=1+Cal+Glad>=2+ (Stan+Cal+Glad) >=7, Kar>=2,NQLD>350&370(AVG),Ross_FN>150&170(AVG),(Townsville GT>=1if kar<2),40% If NQLD>50&70(AVG), Zero otherwise.
Period, last 90 days (27 Aug 2026 to 24 Nov 2026, 2,160 hours).
Binding hours
188
% of period
8.7%
Network as built share
0.0%
Equipment outage share
0.0%
Single-plant limit share
100%
Units in constraints
1
MW in constraints
65
Curtailed while constrained
3.5 GWh
Value of that curtailment
$0.1m

Constraint-hours by cause, per month

Network as builtEquipment outageLimit on a single plant

Constraints that bound in the period

ConstraintHoursCauseLimit typeAEMO description
Q_2+LCCP_RUGBYR140Limit on a single plantSystem StrengthLimit Rugby Run SF to 100%, 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_A39B_RUGBYR135Limit on a single plantSystem StrengthLimit Rugby Run SF to 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+1_R3_RUGBYR134Limit on a single plantSystem StrengthLimit Rugby Run SF to100%,70%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+BSNE_RUGBYR128Limit on a single plantSystem StrengthLimit Rugby Run SF to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_A39_RUGBYR120Limit on a single plantSystem StrengthLimit Rugby Run SF to 80%, 60%, 40%, 20% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+1_R4_RUGBYR112Limit on a single plantSystem StrengthLimit Rugby Run SF to100%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+3+VC_RUGBYR110Limit on a single plantSystem StrengthLimit Rugby Run SF to 80%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+1_R2_RUGBYR19Limit on a single plantSystem StrengthLimit Rugby Run SF to100%,80%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_A39C_RUGBYR13Limit on a single plantSystem StrengthLimit Rugby Run SF to 80%,70%,40%,30%,20% ,1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_2+RSVC_RUGBYR11Limit on a single plantSystem StrengthLimit Rugby Run SF to 100%, 80%, 60%, 40%, 30%, 20%, 1% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville Syncon, NQLD demand, Ross+FNQ demand, NQLD WAMPAC; Zero if it does not meet the condition
Q_STR_NIL_RUGBYR10Limit on a single plantSystem StrengthLimit Rugby Run SF to 100%, 70%, 60% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton/Townsville/Clarke Creek Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition
Q_A19A_RUGBYR10Limit on a single plantSystem StrengthLimit Rugby Run SF to 80%, 40%, 0% dependent on status of Stanwell, Callide B+C, Gladstone, Kareeya, Haughton Syncon, NQLD demand, Ross+FNQ demand; Zero if it does not meet the condition

Units behind it

UnitFuelMWWeightDirection
Rugby Run Solar FarmSolar651.00discharge

Associated outages

SubstationEquipmentStartEndStatusReasonBinding hours (whole outage)
H58_LARC, 275KV_8859LINE 275KV_885921 Sep 2026 07:002 Oct 2026 17:00COMPLETEHV equipt maintenance40
H29_STAN, H24_CALVLINE 275KV_855, CB CPLR_5052, CB 5012, CB FDR_855214 Sep 2026 08:301 Oct 2026 18:00COMPLETEHV equipt commissioning39
H20_BSND, H11_NEBOCB FDR_88462, CB CPLR_5042, LINE 275KV_8846, CB CPLR_50627 Sep 2026 07:0013 Sep 2026 11:30COMPLETEHV equipt commissioning31
H20_BSND, H170_GLNLINE 275KV_8720, CB FDR_87202, CB CPLR_5042, CB FDR_8719213 Sep 2026 12:0020 Sep 2026 17:00COMPLETEHV equipt commissioning22
H11_NEBO, H170_GLNLINE 275KV_8846N, CB CPLR_5062, CB FDR_87202, CB FDR_87192, CB FDR_88462, CB CPLR_502213 Sep 2026 12:0020 Sep 2026 17:00COMPLETEHV equipt commissioning21
H11_NEBO, H35_STHMCB CPLR_5062, CB FDR_8222, LINE 275KV_82211 Sep 2026 07:0011 Sep 2026 17:00COMPLETEHV equipt maintenance5
H35_STHMCB CPLR_5072, CB SVC_5812, SVC 1_H3511 Sep 2026 07:0011 Sep 2026 17:00COMPLETEHV equipt commissioning5
H11_NEBO, H20_BSNDCB CPLR_5062, LINE 275KV_8846, CB CPLR_5042, CB FDR_884629 Sep 2026 07:3013 Sep 2026 13:30COMPLETEHV equipt commissioning5
H35_STHM, H11_NEBOLINE 275KV_822, CB CPLR_5062, CB FDR_822212 Sep 2026 07:0012 Sep 2026 17:00COMPLETEHV equipt maintenance4
H35_STHMCB SVC_5812, CB CPLR_5072, SVC 1_H3512 Sep 2026 07:0012 Sep 2026 17:00COMPLETEHV equipt commissioning4
H13_ROSSSVC 1_H13, CB SVC_5812, CB CPLR_502223 Sep 2026 13:3224 Sep 2026 17:00COMPLETEHV equipt maintenance3
H20_BSNDCB FDR_89252, BUS 1, CB FDR_8202, CB CPLR_5042, CB FDR_8562, CB FDR_88312, CB FDR_893423 Oct 2026 09:306 Oct 2026 16:00COMPLETEHV equipt commissioning3
H6_GNGN, 275KV_814/2CB FDR_8142, LINE 275KV_814/226 Oct 2026 10:0030 Oct 2026 17:00COMPLETEHV equipt maintenance3
H20_BSNDCB FDR_8831226 Oct 2026 08:0026 Oct 2026 16:00COMPLETEHV equipt maintenance3
H58_LARC, 275KV_8859LINE 275KV_885926 Oct 2026 09:0030 Oct 2026 17:00COMPLETEHV equipt maintenance3
H13_ROSSSVC 1_H13, CB SVC_5812, CB CPLR_502223 Sep 2026 20:0024 Sep 2026 12:00COMPLETEHV equipt maintenance2
H29_STANCB 5022, CB FDR_88312, CB FDR_8622, BUS 12, CB FDR_8632, CB FDR_8612, LINE 275KV_8982, CB FDR_86428 Oct 2026 09:008 Oct 2026 16:00COMPLETEHV equipt maintenance1
H29_STANCB FDR_86428 Oct 2026 08:0010 Oct 2026 16:30COMPLETEHV equipt maintenance1
Source: AEMO. Summary built 25 Nov 2026 02:26; data through 25 Nov 2026 01:25 NEM time. “Intervals limited” measures exposure (a binding constraint that includes the unit), not lost output. “Curtailed while constrained” is the unit’s curtailment in intervals when such a constraint was binding, valued at the regional price with negative prices counted as zero. Constraint definitions arrive from AEMO about a month after the event, so recent constraints show “description pending”.