| V::N_NIL_V2 | 95 | Network as built | Transient Stability | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_LTWG_S2 | 21 | Equipment outage | Transient Stability | Out = Lower Tumut to Wagga 330kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, SA accelerates, Yallourn W G1 on 500 kV. |
| V::N_SETB_V2 | 17 | Equipment outage | Transient Stability | Out = one South East - Tailembend 275kV line (Black Range series caps I/S), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_NIL_V1 | 15 | Network as built | Transient Stability | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 220kV. |
| V>>BELML_BAML1_BAML2 | 14 | Equipment outage | Thermal | Out= Ballarat to Elaine to Moorabool 220kV line, avoid O/L Ballarat to Moorabool No.1 220kV line for trip of Ballarat to Moorabool No.2 220kV line, Feedback |
| V>>NIL_ELML_BAML2 | 12 | Network as built | Thermal | Out= Nil, avoid O/L Elaine to Moorabool 220kV line on trip of Ballarat to Moorabool No.2 220kV line, Feedback |
| V::N_KGRC_V1 | 11 | Equipment outage | Transient Stability | Out = Kerang to Red Cliffs 220kV line (or any section in between), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 220kV. |
| V>>NIL_MLGT_MLGT | 8 | Network as built | Thermal | Out = NIL, avoid O/L Moorabool to Geelong #1 or #2 on trip of other Moorabool to Geelong line, Feedback |
| V::N_LTWG_V2 | 7 | Equipment outage | Transient Stability | Out = Lower Tumut to Wagga 330kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates, Yallourn W G1 on 500 kV. |
| V>>6CGH_BEBA_ARWBBA | 6 | Equipment outage | Thermal | Out= 6C, 6G, 6H 330kV lines, avoid O/L Bendigo to Ballarat 220kV line on trip of Ararat to Waubra to Ballarat 220kV line, Feedback |
| V::N_SMSY_V2 | 6 | Equipment outage | Transient Stability | Out = South Morang to Sydenham 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_SMSY_O2 | 5 | Equipment outage | Transient Stability | Out = South Morang to Sydenham 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, Other than VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_ROSM_V2 | 4 | Equipment outage | Transient Stability | Out = Rowville to South Morang 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_NIL_O2 | 4 | Network as built | Transient Stability | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, Other than VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_SMSC_V2 | 4 | Equipment outage | Transient Stability | Out = One South Morang 330 kV series capacitor bank, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V>>BAML1_ELML_BAML2 | 4 | Equipment outage | Thermal | Out= Ballarat to Moorabool No.1 220kV line, avoid O/L Elaine to Moorabool 220kV line on trip of Ballarat to Moorabool No.2 220kV line, Feedback |
| V::N_HWSM_V2 | 3 | Equipment outage | Transient Stability | Out = Hazelwood to South Morang OR Hazelwood to Rowville 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates, Yallourn W G1 on 500 kV. |
| V::N_KGRC_O1 | 3 | Equipment outage | Transient Stability | Out = Kerang to Red Cliffs 220kV line (or any section in between), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, Other than VIC accelerates. Yallourn W G1 on 220kV. |
| V::N_HWCB4_V2 | 2 | Equipment outage | Transient Stability | Out = Hazelwood to Cranbourne No.4 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V>>NIL_BEBA_ARWBBA | 2 | Network as built | Thermal | Out= Nil, avoid O/L Bendigo to Ballarat 220kV line on trip of Ararat to Waubra to Ballarat 220kV line, Feedback |
| V::N_HYSE_V2 | 2 | Equipment outage | Transient Stability | Out = Heywood to South East 275kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates, Yallourn W G1 on 500 kV. |
| V::N_KGRC_V2 | 1 | Equipment outage | Transient Stability | Out = Kerang to Red Cliffs 220kV line (or any section in between), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V>>6CGH_MLGT_MLGT | 1 | Network as built | Thermal | Out = NIL, avoid O/L Moorabool to Geelong #1 or #2 on trip of other Moorabool to Geelong line, Feedback |
| CA_SYDS_59A889E5_1 | 0 | Equipment outage | Thermal | Constraint Automation, O/L BATS_MLTS2_220:LML2:I:220@BATS@VIC for CTG LVAK on trip of MLTS-TGTS 220KV LINE. Generated by STNET[NORCR4] Host NORREGEEMP8(EMPSYD) |
| V::N_SMSC_O2 | 0 | Equipment outage | Transient Stability | Out = One South Morang 330 kV series capacitor bank, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, Other than VIC accelerates. Yallourn W G1 on 500kV. |