Lake Bonney 1 Wind Farm + Lake Bonney 2 Wind Farm + Lake Bonney 3 Wind Farm — system strength
SA · System Strength · V_VS_LB_HY_250
Most frequent constraint: Limiting V-SA + Lake Bonney WF <= 250 MW when SA is at risk of separation. Constraint swamp out when Lake Bonney tripping scheme is O/S
Period, last 90 days (27 Aug 2026 to 24 Nov 2026, 2,160 hours).
Binding hours
22
% of period
1.0%
Network as built share
0.0%
Equipment outage share
3.8%
Single-plant limit share
96%
Units in constraints
3
MW in constraints
278
Curtailed while constrained
0.0 GWh
Value of that curtailment
$0.0m
Network as built: the limit binds with every line and transformer in service. AEMO marks these “Out = Nil”.
Equipment outage: the limit applies only while a named line or transformer is out of service.
Limit on a single plant: AEMO caps one wind or solar farm. Most are system strength limits, which depend on how many coal, gas or hydro units and synchronous condensers are running nearby.
Constraint-hours by cause, per month
Network as builtEquipment outageLimit on a single plant
Constraints that bound in the period
Constraint
Hours
Cause
Limit type
AEMO description
SV_250_LKB_DYN
14
Limit on a single plant
Discretionary
SA to VIC upper contingency limit of 250 MW, considering Lake Bonney WF trip scheme. Limit dynamically reduced when actual flow exceeds limit by at least 10 MW. Limit reduced by amount of exceedance, capped at 25 MW. Constraint swamped if trip scheme O/S
S_ISLE_LKB1+2+3_60
3
Limit on a single plant
Discretionary
Discretionary upper limit on Lake Bonney (1+2+3) windfarms<=60 MW & No. in-service wind turbines for LKB at 41 Turbines.(Note otherwise, LKB 2+3 +1 will be constrained to 0 MW) (Note: swamped when Lake Bonney Tripping scheme is I/S)
V_VS_LB_HY_250
3
Limit on a single plant
System Strength
Limiting V-SA + Lake Bonney WF <= 250 MW when SA is at risk of separation. Constraint swamp out when Lake Bonney tripping scheme is O/S
SV_250_LKB
2
Limit on a single plant
Discretionary
SA to VIC upper contingency limit of 250 MW, considering Lake Bonney WF trip scheme. Constraint swamped if trip scheme O/S
S_V_ROCOF
1
Equipment outage
ROC Frequency
Out = South Australia at credible risk of separation from NEM, limit SA to VIC Heywood interconnection flow to prevent Rate of Change of Frequency exceeding 1 Hz/sec in SA immediately following separation. Considers Lake Bonney WF trip scheme
LINE CPTS_RCTS_220, CAP 2CAP_220, BUS 7MN2, LINE X9
15 Oct 2026 06:30
15 Oct 2026 19:30
COMPLETE
HV equipt maintenance
2
S_EAST
CB CB6609, CB CB8028
15 Oct 2026 07:00
15 Oct 2026 16:00
COMPLETE
HV equipt maintenance
2
Source: AEMO. Summary built 25 Nov 2026 02:56; data through 25 Nov 2026 01:55 NEM time. “Intervals limited” measures exposure (a binding constraint that includes the unit), not lost output. “Curtailed while constrained” is the unit’s curtailment in intervals when such a constraint was binding, valued at the regional price with negative prices counted as zero. Constraint definitions arrive from AEMO about a month after the event, so recent constraints show “description pending”.