| V^^V_NIL_KGTS | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 105 | discharge | Out= Nil, avoid voltage collapse for loss of Horsham - Murra Warra - Kiamal 220kV line. Murraylink VFRB disabled. Swamp if Murraylink VFRB enabled. |
| V^^V_6CGH_KGTS | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 98 | discharge | Out= 6C, 6G, 6H 330kV lines, avoid voltage collapse for loss of Horsham - Murra Warra - Kiamal 220kV line. Murraylink VFRB disabled. Swamp if Murraylink VFRB enabled |
| V_CRWARP_FLT_75 | Carwarp Solar Farm — system strength | 79 | discharge | Limit Carwarp solar farm upper limit to 75 MW to manage post contingent voltage oscillation |
| V_CRWARP_FLT_0 | Carwarp Solar Farm — system strength | 48 | discharge | Limit Carwarp solar farm upper limit to 0 MW to manage post contingent voltage oscillation |
| VS_HEY_600_TEST | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 36 | charge | Out = Nil, Vic to SA on Heywood limit of 600 MW, limit for testing of Heywood interconnection upgrade |
| V>>BELML_BAML1_BAML2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 14 | discharge | Out= Ballarat to Elaine to Moorabool 220kV line, avoid O/L Ballarat to Moorabool No.1 220kV line for trip of Ballarat to Moorabool No.2 220kV line, Feedback |
| V^^V_BDBU_KGTS | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 12 | discharge | Out = Bundey to Buronga (6F) 330kV line, avoid voltage collapse for loss of Horsham - Murra Warra - Kiamal 220kV line. Murraylink VFRB disabled. Swamp if Murraylink VFRB enabled. |
| V>>BDBU_ELML_BAML2 | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 12 | discharge | Out = Bundey to Buronga (6F) 330kV line, avoid O/L Elaine to Moorabool 220kV line on trip of Ballarat to Moorabool No.2 220kV line, Feedback |
| V>>NIL_ELML_BAML2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 12 | discharge | Out= Nil, avoid O/L Elaine to Moorabool 220kV line on trip of Ballarat to Moorabool No.2 220kV line, Feedback |
| V>>DDGN_GEDD_GNDD | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 9 | discharge | Out = Glenrowan to Dederang No.1 or No.3 220kV line, avoid O/L Goorambat East to Dederang 220kV line on loss of remaining Glenrowan to Dederang 220kV line, feedback |
| V>>NIL_MLGT_MLGT | Victoria: transient stability, Hazelwood–South Morang 500 kV | 8 | discharge | Out = NIL, avoid O/L Moorabool to Geelong #1 or #2 on trip of other Moorabool to Geelong line, Feedback |
| V>>6CGH_BEBA_ARWBBA | Victoria: transient stability, Hazelwood–South Morang 500 kV | 6 | discharge | Out= 6C, 6G, 6H 330kV lines, avoid O/L Bendigo to Ballarat 220kV line on trip of Ararat to Waubra to Ballarat 220kV line, Feedback |
| V>>6CGH_ELML_BAML2 | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 5 | discharge | Out= 6C, 6G, 6H 330kV lines, avoid O/L Elaine to Moorabool 220kV line on trip of Ballarat to Moorabool No.2 220kV line, Feedback |
| V>>NIL_WBBA_KGBE | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 4 | discharge | Out= Nil, avoid O/L Waubra to Ballarat 220kV line on trip of Kerang to Bendigo 220kV line, Feedback |
| V_NWVIC_GEN_1100 | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 4 | discharge | 1100MW upper limit on IBR within North West Victoria (Bendigo-Ballarat-Red Cliffs 220kV area) |