| V::N_NIL_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 95 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V^^N_NIL_1 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 33 | charge | Out = Nil, avoid voltage collapse around Murray for loss of all APD potlines |
| V::N_LTWG_S2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 21 | charge | Out = Lower Tumut to Wagga 330kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, SA accelerates, Yallourn W G1 on 500 kV. |
| V::N_SETB_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 17 | charge | Out = one South East - Tailembend 275kV line (Black Range series caps I/S), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_NIL_V1 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 15 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 220kV. |
| V::N_KGRC_V1 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 11 | charge | Out = Kerang to Red Cliffs 220kV line (or any section in between), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 220kV. |
| V^^N_SDUT_1 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 11 | charge | Out = Stockdill to Upper Tumut (1) line, avoid voltage collapse around Murray for loss of all APD potlines |
| V^^N_BADP_1 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 10 | charge | Out = Balranald to Darlington Point (X5) 220kV line, avoid voltage collapse around Murray for loss of all APD potlines |
| V^^N_GRYS_1 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 7 | charge | Out = Gullen Range to Yass (3J), avoid voltage collapse around Murray for loss of all APD potlines |
| V::N_LTWG_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 7 | charge | Out = Lower Tumut to Wagga 330kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates, Yallourn W G1 on 500 kV. |
| V>>6CGH_BEBA_ARWBBA | Victoria: transient stability, Hazelwood–South Morang 500 kV | 6 | discharge | Out= 6C, 6G, 6H 330kV lines, avoid O/L Bendigo to Ballarat 220kV line on trip of Ararat to Waubra to Ballarat 220kV line, Feedback |
| V::N_SMSY_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 6 | charge | Out = South Morang to Sydenham 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_SMSY_O2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 5 | charge | Out = South Morang to Sydenham 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, Other than VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_ROSM_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 4 | charge | Out = Rowville to South Morang 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_NIL_O2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 4 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, Other than VIC accelerates. Yallourn W G1 on 500kV. |