| N>>NIL_060_051 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 357 | discharge | Out= Nil, avoid O/L Jindera to Wodonga (60) 330kV line using 15 mins rating on trip of Wagga to Lower Tumut (051) 330kV line, Feedback |
| N>>6CGH_060_051 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 244 | discharge | Out= 6C, 6G, 6H 330kV lines, avoid O/L Jindera to Wodonga (60) 330kV line using 15 mins rating on trip of Wagga to Lower Tumut (051) 330kV line, Feedback |
| N^^N_6CGH_WGLT | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 182 | discharge | Out=Nil, limit Wagga to Lower Tumut (51) 330kV line flow to avoid voltage collapse post contingency trip of line 51, Feedback |
| N^^N_NIL_WGLT | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 178 | discharge | Out=Nil, limit Wagga to Lower Tumut (051) 330kV line flow to avoid voltage collapse post contingency trip of line 51, Feedback |
| N::N_CNCW_2 | Snowy to NSW: transient stability limits (Yass–Bannaby–Marulan) | 145 | discharge | Out = Canberra-Capital (6) line, stability limit (Snowy-NSW) for critical fault of one 330kV line between Yass and Bannaby/Marulan |
| N::N_SDUT_2 | Snowy to NSW: transient stability limits (Yass–Bannaby–Marulan) | 111 | discharge | Out = Upper Tumut-Stockdill (1) 330kV line, stability limit (Snowy-NSW) for fault of various location between Yass-South Morang area |
| N^^N_NIL_LTWG | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 66 | charge | Out=Nil, limit Lower Tumut to Wagga 330kV line flow to avoid voltage collapse post contingency trip of line 51, Feedback |
| V>>N_NIL_65_051 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 34 | discharge | Out = NIL, avoid O/L Murray to Upper Tumut (65) on trip of Wagga to Lower Tumut (051) line, Feedback |
| N>>BDBU_060_051 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 18 | discharge | Out= Bundey to Buronga (6F) 330kV Line, avoid O/L Jindera to Wodonga (60) 330kV line on trip of Wagga to Lower Tumut (051) 330kV line, Feedback |
| N::N_GRRP_2 | Snowy to NSW: transient stability limits (Yass–Bannaby–Marulan) | 4 | discharge | Out = Gullen Range to Rye Park (3P), stability limit (Snowy-NSW) for loss of Yass-Marulan (4/5) 330kV line |
| N::N_DTKV_2 | Snowy to NSW: transient stability limits (Yass–Bannaby–Marulan) | 2 | discharge | Out = Dapto - Kangaroo Valley (18) 330kV line, transient stability limit (Snowy-NSW) for loss of one 330kV line between Yass and Bannaby/Marulan with summated flow on 4+5+61 <=1500 |
| N>NIL_9R4_62 | Mulwala to Corowa (996/2) | 1 | charge | Out= NIL, avoid O/L Finley to Mulwala (9R4) 132kV line on trip of Walla Walla to Jindera (62) 330kV line, Feedback |
| N>>NIL_996_62 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 1 | charge | Out = Nil, avoid Wagga to ANM (996) 132kV line O/L on Walla Walla to Jindera (62) 330kV line trip; Feedback (Note: constraint swamped when 996 is O/S) |
| N>>V_6CGH_65_66 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 0 | charge | Out = 6C, 6G, 6H 330kV lines, avoid Upper Tumut to Murray(65) using 15 mins rating O/L on Lower Tumut to Murray(66) trip; (Note: constraint is swamped out if TL 64 is O/S) |
| N>>V_DDMS_051_67_N | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 0 | discharge | Out= Dederang to Murray (67 or 68) 330 kV line, avoid O/L Wagga to Lower Tumut (051) 330kV line on trip of the remaining Dederang to Murray 330kV line, Feedback |