| N>NIL_969 | North-west NSW: Gunnedah–Tamworth 132 kV | 412 | discharge | Out= Nil, avoid O/L Gunnedah to Tamworth (969) on trip of Nil, Feedback. Metering is used as specified in OM520 [Note: swamped with 96M or 9UJ or 9UH or 9U3/2 is O/S] |
| N>>NIL_964_84_S | NSW mid-north coast: Port Macquarie–Herons Creek 132 kV | 259 | discharge | Out= NIL, avoid O/L Port Macquarie to Herons Creek Tee (964/2) on trip of Tamworth to Liddell (84) line, Feedback |
| N>96M_969_NIL | North-west NSW: Gunnedah–Tamworth 132 kV | 30 | discharge | Out= Moree to Narrabri (96M) 132kV line |
| N>X-968+96M_969_NIL | North-west NSW: Gunnedah–Tamworth 132 kV | 8 | discharge | Out= 968 (Tamworth to Narrabri) 132 kV Line and 96M(Narrabri to Moree), avoid O/L on 969 (Gunnedah to Tamworth) 132 kV on Nil trip, Feedback |
| N>9UH_969_NIL | North-west NSW: Gunnedah–Tamworth 132 kV | 8 | discharge | Out= Any one 132kV feeder between Narrabri to Gunnedah Solar Farm (9UH, 9UJ, 9U3/2), avoid O/L Gunnedah to Tamworth (969) 132kV line on trip of Nil, Feedback |
| N>>NIL_33_34 | Bayswater to Liddell (33 or 34) O/L on loss of other Bayswater to | 6 | charge | Out= Nil, avoid Bayswater to Liddell (33 or 34) O/L on loss of other Bayswater to Liddell (34 or 33), Feedback |
| N>>965_9W2_9W8 | NSW mid-north coast: Port Macquarie–Herons Creek 132 kV | 6 | discharge | Out= Armidale to Kempsey (965), avoid O/L Raliegh to Kempsey 132kV line on trip of Coffs Harbour to Boambee (9W8) 132kV line, Feedback |
| N>>9W7_9W2_965 | NSW mid-north coast: Port Macquarie–Herons Creek 132 kV | 5 | discharge | Out= One of Coffs Harbour to Kempsey (9W5 or 9W6 or 9W7 or 9W8), avoid O/L Raliegh to Kempsey (9W2) 132kV line on trip of Armidale to Kempsey (965) 132kV line, Feedback |
| N>9U2_969_NIL | North-west NSW: Gunnedah–Tamworth 132 kV | 4 | discharge | Out= 9U2 (Moree to Inverell ) 132kV line, avoid O/L on 969 (Gunnedah to Tamworth) 132 kV on Nil trip, Feedback |
| N>>33_34_QMAX_N | Bayswater to Liddell (33 or 34) O/L on loss of other Bayswater to | 3 | charge | Out = Bayswater to Liddell(33 or 34), avoid O/L Bayswater to Liddell(33 or 34) on trip of QLD largest generation, Feedback |
| N>>81_964_82 | NSW mid-north coast: Port Macquarie–Herons Creek 132 kV | 3 | discharge | Out = Liddell to Newcastle (81) line, avoid O/L Port Macquarie to Herron Creek Tee (964/2) on trip of Liddell to Tomago (82) line, (Note: Swamps if 964 O/S) |
| N>>34+5A5_33_32 | Bayswater to Liddell (33 or 34) O/L on loss of other Bayswater to | 2 | charge | Out= Mt. Piper-Wollar (5A5) and Bayswater to Liddell (33 or 34) line, avoid O/L Bayswater to Liddell (33 or 34) 330kV line on trip of Bayswater to Sydney West (32) 330kV line, Feedback |
| N>>81_964_84 | NSW mid-north coast: Port Macquarie–Herons Creek 132 kV | 0 | discharge | Out = Liddell to Newcastle (81) line, avoid O/L Port Macquarie to Herron Creek Tee (964/2) on trip of Liddell to Tamworth (84) line,(Note: Swamps if 964 O/S) |
| N>>NIL_964_88_S | NSW mid-north coast: Port Macquarie–Herons Creek 132 kV | 0 | discharge | Out= NIL, avoid O/L Port Macquarie to Herons Creek Tee (964/2) on trip of Tamworth to Muswellbrook (88) line, Feedback |
| N_GNNDHSF1_0INV | North-west NSW: Gunnedah–Tamworth 132 kV | 0 | discharge | Gunnedah Solar Farm inverter limit of zero. Constraint to violate if Gunnedah Solar Farm inverter availability greater than zero. Swamp out otherwise. DS only |