| V::N_NIL_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 95 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V_SH_DD_MAC_FLT_965 | Stockyard Hill, Dundonnell, Macarthur, Hawkesdale, and Ryan Corner wind farm total output | 24 | discharge | Limit Stockyard Hill, Dundonnell, Macarthur, Hawkesdale, and Ryan Corner wind farm total output to 965 MW if Heywood flow is above 500 MW (SA to VIC direction). Swamp otherwise. This is to manage voltage oscillation. |
| V::N_LTWG_S2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 21 | charge | Out = Lower Tumut to Wagga 330kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, SA accelerates, Yallourn W G1 on 500 kV. |
| V::N_SETB_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 17 | charge | Out = one South East - Tailembend 275kV line (Black Range series caps I/S), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_NIL_V1 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 15 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 220kV. |
| V::N_KGRC_V1 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 11 | charge | Out = Kerang to Red Cliffs 220kV line (or any section in between), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 220kV. |
| V>>NIL_MLGT_MLGT | Victoria: transient stability, Hazelwood–South Morang 500 kV | 8 | discharge | Out = NIL, avoid O/L Moorabool to Geelong #1 or #2 on trip of other Moorabool to Geelong line, Feedback |
| V::N_LTWG_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 7 | charge | Out = Lower Tumut to Wagga 330kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates, Yallourn W G1 on 500 kV. |
| V::N_SMSY_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 6 | charge | Out = South Morang to Sydenham 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_SMSY_O2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 5 | charge | Out = South Morang to Sydenham 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, Other than VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_ROSM_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 4 | charge | Out = Rowville to South Morang 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_NIL_O2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 4 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, Other than VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_SMSC_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 4 | charge | Out = One South Morang 330 kV series capacitor bank, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_HWSM_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 3 | charge | Out = Hazelwood to South Morang OR Hazelwood to Rowville 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates, Yallourn W G1 on 500 kV. |
| V::N_KGRC_O1 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 3 | charge | Out = Kerang to Red Cliffs 220kV line (or any section in between), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, Other than VIC accelerates. Yallourn W G1 on 220kV. |