| V::N_NIL_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 95 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_LTWG_S2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 21 | charge | Out = Lower Tumut to Wagga 330kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, SA accelerates, Yallourn W G1 on 500 kV. |
| V::N_SETB_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 17 | charge | Out = one South East - Tailembend 275kV line (Black Range series caps I/S), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_NIL_V1 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 15 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 220kV. |
| V>>BELML_BAML1_BAML2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 14 | discharge | Out= Ballarat to Elaine to Moorabool 220kV line, avoid O/L Ballarat to Moorabool No.1 220kV line for trip of Ballarat to Moorabool No.2 220kV line, Feedback |
| C_V_LANCSF1_040 | Lancaster Solar Farm — commissioning (zero MW) | 13 | discharge | Commissioning / hold point constraint for Lancaster Solar Farm of 40 MW - HP2 |
| V>>BDBU_ELML_BAML2 | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 12 | discharge | Out = Bundey to Buronga (6F) 330kV line, avoid O/L Elaine to Moorabool 220kV line on trip of Ballarat to Moorabool No.2 220kV line, Feedback |
| V>>NIL_ELML_BAML2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 12 | discharge | Out= Nil, avoid O/L Elaine to Moorabool 220kV line on trip of Ballarat to Moorabool No.2 220kV line, Feedback |
| V::N_KGRC_V1 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 11 | charge | Out = Kerang to Red Cliffs 220kV line (or any section in between), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 220kV. |
| V>>DDGN_GEDD_GNDD | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 9 | discharge | Out = Glenrowan to Dederang No.1 or No.3 220kV line, avoid O/L Goorambat East to Dederang 220kV line on loss of remaining Glenrowan to Dederang 220kV line, feedback |
| V>>NIL_MLGT_MLGT | Victoria: transient stability, Hazelwood–South Morang 500 kV | 8 | discharge | Out = NIL, avoid O/L Moorabool to Geelong #1 or #2 on trip of other Moorabool to Geelong line, Feedback |
| V::N_LTWG_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 7 | charge | Out = Lower Tumut to Wagga 330kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates, Yallourn W G1 on 500 kV. |
| V>>6CGH_BEBA_ARWBBA | Victoria: transient stability, Hazelwood–South Morang 500 kV | 6 | discharge | Out= 6C, 6G, 6H 330kV lines, avoid O/L Bendigo to Ballarat 220kV line on trip of Ararat to Waubra to Ballarat 220kV line, Feedback |
| V::N_SMSY_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 6 | charge | Out = South Morang to Sydenham 500kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V>>6CGH_ELML_BAML2 | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 5 | discharge | Out= 6C, 6G, 6H 330kV lines, avoid O/L Elaine to Moorabool 220kV line on trip of Ballarat to Moorabool No.2 220kV line, Feedback |