| N^^N_6CGH_WGLT | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 182 | charge | Out=Nil, limit Wagga to Lower Tumut (51) 330kV line flow to avoid voltage collapse post contingency trip of line 51, Feedback |
| N^^N_NIL_WGLT | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 178 | charge | Out=Nil, limit Wagga to Lower Tumut (051) 330kV line flow to avoid voltage collapse post contingency trip of line 51, Feedback |
| V::N_NIL_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 95 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| N^^N_NIL_LTWG | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 66 | discharge | Out=Nil, limit Lower Tumut to Wagga 330kV line flow to avoid voltage collapse post contingency trip of line 51, Feedback |
| N^^V_CNCW_1 | Southern NSW: voltage stability for loss of the largest Victorian unit or Basslink | 49 | discharge | Out = Canberra-Capital (6) or Kangaroo Valley to Capital (3W) or Dapto-Kangaroo Valley (18), avoid voltage collapse at Darlington Point for loss of the largest Vic generating unit or Basslink |
| N^^V_NIL_1 | Southern NSW: voltage stability for loss of the largest Victorian unit or Basslink | 41 | discharge | Out = Nil, avoid voltage collapse at Southern NSW for loss of the largest Vic generating unit or Basslink |
| V^^N_NIL_1 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 33 | charge | Out = Nil, avoid voltage collapse around Murray for loss of all APD potlines |
| V::N_LTWG_S2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 21 | charge | Out = Lower Tumut to Wagga 330kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, SA accelerates, Yallourn W G1 on 500 kV. |
| N^^V_MLNK_1 | Southern NSW: voltage stability for loss of the largest Victorian unit or Basslink | 19 | discharge | Out = Murraylink, avoid voltage collapse at Southern NSW for loss of the largest Vic generating unit or Basslink |
| V::N_SETB_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 17 | charge | Out = one South East - Tailembend 275kV line (Black Range series caps I/S), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V::N_NIL_V1 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 15 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 220kV. |
| V::N_KGRC_V1 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 11 | charge | Out = Kerang to Red Cliffs 220kV line (or any section in between), prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 220kV. |
| V^^N_SDUT_1 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 11 | charge | Out = Stockdill to Upper Tumut (1) line, avoid voltage collapse around Murray for loss of all APD potlines |
| V^^N_BADP_1 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 10 | charge | Out = Balranald to Darlington Point (X5) 220kV line, avoid voltage collapse around Murray for loss of all APD potlines |
| N^^V_BADP_1 | Southern NSW: voltage stability for loss of the largest Victorian unit or Basslink | 10 | discharge | Out = Balranald to Darlington Point (X5) 220kV line, avoid voltage collapse at Darlington Point for loss of the largest Vic generating unit or Basslink |