| S>>BWMP_TWPA_TPRS | Manage voltage collapse in northern SA for the trip of one 275kV line | 42 | discharge | Out= Blyth West- Munno Para 275kV line with Blyth West CB8002 OPEN, avoid O/L Templers-Roseworthy 132kV line on trip of Templers West-Para 275kV line, Feedback |
| S>>NIL_TWPA_TPRS | Manage voltage collapse in northern SA for the trip of one 275kV line | 16 | discharge | Out= NIL, avoid O/L Templers-Roseworthy 132kV line on trip of Templers West-Para 275kV line, Feedback |
| S>>BWMP_DVBR_RHBG-T | Manage voltage collapse in northern SA for the trip of one 275kV line | 3 | discharge | Out= Blyth West- Munno Para 275kV line with Blyth West CB8002 OPEN, avoid O/L Redhill- Brinkworth 132kV T line on trip of Davenport-Brinkworth 275kV line, Feedback |
| S>>BWMP_BRTW_WTTP | Manage voltage collapse in northern SA for the trip of one 275kV line | 3 | discharge | Out= Blyth West- Munno Para 275kV line with Blyth West CB8002 OPEN, avoid O/L Waterloo-Templers 132kV line on trip of Brinkworth-Templers West 275kV line, Feedback |
| S>>BWMP_HUWT_RHBG-T | Manage voltage collapse in northern SA for the trip of one 275kV line | 3 | discharge | Out= Blyth West- Munno Para 275kV line with Blyth West CB8002 OPEN, avoid O/L Redhill-Brinkworth 132kV T line on trip of Hummocks-Waterloo 132kV line, Feedback |
| S>>BRTW_BWPA_WTTP | Manage voltage collapse in northern SA for the trip of one 275kV line | 3 | discharge | Out= Brinkworth- Templers West 275kV line, avoid O/L Waterloo-Templers 132kV on trip of Blyth West-Munno Para 275kV line, Feedback |
| S>>NIL_BWMP_WTTP | Manage voltage collapse in northern SA for the trip of one 275kV line | 2 | discharge | Out= Nil, avoid O/L Waterloo - Templers 132kV on trip of Blyth West- Munno Para 275kV line, Feedback |
| S_DVCL_270 | Out=Davenport-Corraberra Hill 275kV line OR Davenport-Cultana 275 kV | 1 | discharge | Out=Davenport-Corraberra Hill 275kV line OR Davenport-Cultana 275 kV line 2, discretionary upper limit for Cathedral Rocks WF + Mount Millar WF + Lincoln Gap WF+ Lincoln Gap Battery+ Pt Lincoln GTs <= 270 MW |
| S>>CNRB_TWPA_TPRS | Manage voltage collapse in northern SA for the trip of one 275kV line | 1 | discharge | Out= Canowie-Robertstown 275kV line, avoid O/L Templers-Roseworthy 132kV line on trip of Templers West-Para 275kV line, Feedback |
| S>>CNRB_BWPA_RHBR-T | Manage voltage collapse in northern SA for the trip of one 275kV line | 1 | discharge | Out= Canowie-Robertstown 275kV line, avoid O/L Redhill-Brinkworth T 132kV line on trip of Blyth West-Munno Para 275kV line, Feedback |
| S>>NIL_BRTW_WTTP | Manage voltage collapse in northern SA for the trip of one 275kV line | 0 | discharge | Out= Nil, avoid O/L Waterloo - Templers 132kV on trip of Brinkworth - Templers West 275kV line, Feedback |
| S>HUWT_BWPA_RHBR-T | Manage voltage collapse in northern SA for the trip of one 275kV line | 0 | discharge | Out= Hummocks-Waterloo 132kV line, avoid O/L Redhill-Brinkworth T 132kV line on trip of Blyth West-Munno Para 275kV line, Feedback |
| S>>BWMP_RBTU_WTTP | Manage voltage collapse in northern SA for the trip of one 275kV line | 0 | discharge | Out= Blyth West- Munno Para 275kV line with Blyth West CB8002 OPEN, avoid O/L Waterloo-Templers 132kV line on trip of Robertstown-Tungkillo 275kV line 1 or 2, Feedback |
| S>>PATW_RBTU_TPRS | Manage voltage collapse in northern SA for the trip of one 275kV line | 0 | discharge | Out= Para-Templers West 275kV line, avoid O/L Templers-Roseworthy 132kV line on trip of Robertstown-Tungkillo 275kV line 1 or 2, Feedback |
| S>BRDV_BWPA_RHBR | Manage voltage collapse in northern SA for the trip of one 275kV line | 0 | discharge | Out= Brinkworth - Davenport 275kV line, avoid O/L Redhill tee - Brinkworth 132kV on trip of Blyth West-Munno Para 275kV line, Feedback |