| N>>NIL_060_051 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 357 | discharge | Out= Nil, avoid O/L Jindera to Wodonga (60) 330kV line using 15 mins rating on trip of Wagga to Lower Tumut (051) 330kV line, Feedback |
| N>>6CGH_060_051 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 244 | discharge | Out= 6C, 6G, 6H 330kV lines, avoid O/L Jindera to Wodonga (60) 330kV line using 15 mins rating on trip of Wagga to Lower Tumut (051) 330kV line, Feedback |
| N^^N_6CGH_WGLT | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 182 | discharge | Out=Nil, limit Wagga to Lower Tumut (51) 330kV line flow to avoid voltage collapse post contingency trip of line 51, Feedback |
| N^^N_NIL_WGLT | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 178 | discharge | Out=Nil, limit Wagga to Lower Tumut (051) 330kV line flow to avoid voltage collapse post contingency trip of line 51, Feedback |
| V^^V_NIL_KGTS | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 105 | discharge | Out= Nil, avoid voltage collapse for loss of Horsham - Murra Warra - Kiamal 220kV line. Murraylink VFRB disabled. Swamp if Murraylink VFRB enabled. |
| V^^V_6CGH_KGTS | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 98 | discharge | Out= 6C, 6G, 6H 330kV lines, avoid voltage collapse for loss of Horsham - Murra Warra - Kiamal 220kV line. Murraylink VFRB disabled. Swamp if Murraylink VFRB enabled |
| V::N_NIL_V2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 95 | charge | Out = NIL, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, VIC accelerates. Yallourn W G1 on 500kV. |
| V_YATPSF_FLT_25 | Yatpool Solar Farm — system strength | 76 | discharge | Limit Yatpool solar farm upper limit to 25 MW to manage post contingent voltage oscillation |
| N^^N_NIL_LTWG | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 66 | charge | Out=Nil, limit Lower Tumut to Wagga 330kV line flow to avoid voltage collapse post contingency trip of line 51, Feedback |
| V^^V_MLNK_KGTS | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 64 | discharge | Out= Murraylink, avoid voltage collapse for loss of Horsham - Murra Warra - Kiamal 220kV line |
| VS_HEY_600_TEST | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 36 | charge | Out = Nil, Vic to SA on Heywood limit of 600 MW, limit for testing of Heywood interconnection upgrade |
| V^^N_NIL_1 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 33 | charge | Out = Nil, avoid voltage collapse around Murray for loss of all APD potlines |
| I_6F_NS_150 | North-west Victoria: voltage stability, Horsham–Murra Warra–Kiamal 220 kV | 28 | discharge | Discretionary limit of 150 MW on Buronga to Bundey (6F) 330 kV Line (NSW to SA) |
| V::N_LTWG_S2 | Victoria: transient stability, Hazelwood–South Morang 500 kV | 21 | charge | Out = Lower Tumut to Wagga 330kV line, prevent transient instability for fault and trip of a HWTS-SMTS 500 kV line, SA accelerates, Yallourn W G1 on 500 kV. |
| N>>BDBU_060_051 | Southern NSW: Jindera–Wodonga and Wagga–Lower Tumut 330 kV | 18 | discharge | Out= Bundey to Buronga (6F) 330kV Line, avoid O/L Jindera to Wodonga (60) 330kV line on trip of Wagga to Lower Tumut (051) 330kV line, Feedback |